Views: 0 Author: Site Editor Publish Time: 2020-10-01 Origin: Site
1) The basic principle of the steam delivery pipe is to have a downward slope of 1/200~1/300 along the direction of steam flow. In this way, the condensed water and steam can flow in the same direction, which is easy to prevent water hammer and facilitate the removal of condensate.
2) Generally, it is not allowed to have bends or recesses in the middle of the pipeline. If these stagnation points cannot be avoided due to the limitation of the installation location and environment, a steam trap should be installed there.
3) In order to prevent water hammer and supply high-quality steam, when steam is delivered from the steam delivery pipe to the steam-using equipment through the steam branch pipe, in principle, the steam branch pipe should be installed above the main steam pipe.